Single Core Rubber/Crosslinked Polymer Insulated Cables H05G-K, H05Z-K, H07G-K, H07Z-K

Construction

Conductor: Fine Stranded Flexible Copper to VDE 0295 IEC 60228

Insulation/ Sheath : H05G-K / H07G-K Rubber compound E13, Halogen Free, DIN VDE -282, H05Z-K / H07Z-K Cross-linked Polymer Compound, Flame Retardant, Low Smoke Halogen free EI5 LSZH

Colour: Green/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White, Green, Yellow or Other Colours

Flame Propagation : Flame Retardant Test as Per IEC 60332-1

Features

> Special Heat Resistant Rubber/Thermosetting Insulation
> High Current Carrying Capacity
> High Elasticity
> Excellent Resistant to Moisture, Abrasion, Grace, Oil
> Longer Flex Life
> Excellent Mechanical & Electrical Properties
> Harmonized Acc. to European Standards

Technical Data

Operating Temperature : -40C to +110C (H05G-K/H07G-K),  -30°C to +90C (H05Z-K/H07Z-K)

Nominal Voltage: H05G-K/H05Z-K : 300/500 V,  H07G-K/H07Z-K : 450/750 V

Test Voltage: H05G-K/H05Z-K: 2000 V, H07G-K/H07Z-K : 2500 V

Insulation Resistance: Min. 10 ΜΩ x km

Min. Bending Radius: 5 x Cable Diameter

Application

For Inside Wiring of Switch Board and Distributors as Well as of Operating Parts Such as in or on Lights with Normal Voltage Up to 1100 V.
Fixed Installation in Conduits And Under Plaster, for Appliance Wiring and Distribution Stations for Wiring of Lamps, Devices, Switchgear Cabinets
and Distribution Boxes.
Standard length Cable Packing : Coils 100 and 200 m in Carton Boxes, Reels.

H05G-K / H05Z-K (300/500 V)
Size in mm²Nos/Dia. (Nom.)Insulation Thickness
in mm (Nom.)
Outer Dia in
mm (Appx.)
Max. C.R in
ohm/km Copper
0.516/0.2000.602.1039.00
0.7524/0.2000.602.2026.00
132/0.2000.602.7019.50

 

H07G-K / H07Z-K (450/750 V)
Size in mm²Nos/Dia. (Nom.)Insulation Thickness
in mm (Nom.)
Outer Dia in
mm (Appx.)
Max. C.R in
ohm/km Copper
1.530/0.2500.703.2513.30
2.550/0.2500.803.807.98
456/0.3000.804.504.95
684/0.3000.805.253.30
10140/0.3001.006.501.91
16224/0.3001.008.001.21
25350/0.3001.2010.100.780
35490/0.3001.2011.300.554
50703/0.3001.4013.500.386
70988/0.3001.4015.300.272
951349/0.3001.6018.000.206
120608/0.5001.6019.800.161
150760/0.5001.8022.300.129
185943/0.5002.0023.900.106
2401225/0.5002.2026.800.0801

Note : The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of
conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360 or Ul83.