DC SOLAR CABLE
Features
- Mineral Oil Resistance
- Acid and Alkaline Resistance
- Ammonia Resistance
- Weather Resistance
Technical Detail
- Generally Conforming to EN 50618
- AC 0.6 / 1.0 kV
- DC 1.8 kV
- Fine Wire Tinned Copper Conductor according to IEC 60228 cl. 5.
- XLPO (cross linkable, halogen free, flame retardant) compound for core insulation.
- XLPO (cross linkable, halogen free, flame retardant) compound for Sheath over insulation.
- Red, Black, Black with Red Strip
Application
Solar cables are intented for use in photovoltaic power supply systems and similar applications as free hanging, movable, fixed installation and buried in ground in constructional covered systems. The cables can be used indoor, outdoor, in hazard explosion areas, in industry and agriculture.
CABLE DESIGN PARAMETERS | |||||
---|---|---|---|---|---|
Nominal Cross-Sectional (sq.mm.) |
Approx. Cable Diameter (mm) | Current carrying capacity according to method of installation | Max. Conductor Resistance at 20°C, (Ω/Km) | ||
Single cable free in air (A) | Single cable on a surface (A) | Two loaded touching, on a surface (A) |
|||
1.5 | 4.7 | 30 | 29 | 24 | 13.7 |
2.5 | 5.1 | 41 | 39 | 33 | 8.21 |
4 | 5.6 | 55 | 52 | 44 | 5.09 |
6 | 6.1 | 70 | 67 | 57 | 3.39 |
10 | 7.1 | 98 | 93 | 79 | 1.95 |
16 | 8.3 | 132 | 125 | 107 | 1.24 |
25 | 10.1 | 176 | 167 | 142 | 0.795 |
35 | 11.5 | 218 | 207 | 176 | 0.565 |
50 | 13.3 | 276 | 262 | 221 | 0.393 |
70 | 15.2 | 347 | 330 | 278 | 0.277 |
95 | 16.9 | 416 | 395 | 333 | 0.210 |
120 | 18.7 | 488 | 464 | 390 | 0.164 |
150 | 20.9 | 566 | 538 | 453 | 0.132 |
185 | 23.2 | 644 | 612 | 515 | 0.108 |
240 | 26.1 | 755 | 736 | 620 | 0.0817 |