Round Aluminium Cable
Features
- Excellent resistant to moisture & abrasion
- Long Life
- Excellent mechanical & electrical properties
- High Thermally Stable Insulation
Technical Detail
- IS 694 Marks Latest
- Up to and including 1100V
- As per customer requirement
- Aluminium Conductor as per IS:8130
- As per IS 5831
- Black
Application
Round Aluminium cables are used for outdoor installation in wet location, laid
direct in ground where mechanical damages are expected to occur
PVC INSULATED & SHEATHED ROUND UNARMOURED ALUMINIUM CABLES UP TO 1100 V. GENERALLY CONFORMING TO IS 694:2010 | |||||||||
---|---|---|---|---|---|---|---|---|---|
Nominal c/s Area Of conductor In Sq.mm. | conductor construction No./mm. | Nominal Insulatio Thickness In mm. | Approx. Core Dia.In mm | Outer Sheath Nominal Thickness In mm. | Approx.Overall Dimensions | Current Rating At 40 °C In Amps. | Max.D/C Resistance @ 20 °C Ohm/km. | ||
3 CORE | 4 CORE | 3 CORE | 4 CORE | ||||||
4.00 | 1/2.25 | 0.8 | 3.8 | 1.3 | 1.4 | 11.40 | 12.85 | 19 | 7.41 |
6.00 | 1/2.76 | 0.8 | 4.5 | 1.4 | 1.4 | 12.45 | 14.50 | 24 | 4.61 |
10.00 | 1/3.57 | 1.0 | 5.5 | 1.5 | 1.6 | 14.40 | 16.00 | 32 | 3.08 |
16.00 | 1/4.50 | 1.0 | 6.7 | 1.6 | 1.6 | 17.50 | 20.40 | 44 | 1.91 |
25.00 | 1/5.65 | 1.2 | 8.0 | 1.7 | 1.8 | 20.50 | 23.00 | 49 | 1.20 |
35.00 | 1/6.68 | 1.2 | 9.4 | 1.8 | 1.9 | 23.75 | 27.30 | 61 | 0.868 |